Parameter

Description

TRAVEL_COUNT_LIM

Limit for TRAVEL_COUNT; at 0
TRAVEL_COUNT_LIM will not be processed.
If the LIMIT value is exceeded, the corres-
ponding bit will be set in CHECK_BACK.

TRAVEL_TIME_CLOSE_OPEN

Limit for the time in seconds between the
change of the state from CLOSE to
OPEN; with 0, the time is not processed.
If the value is exceeded, the corresponding
bit will be set in CHECK_BACK. Times less
than 2 seconds cannot be monitored.

TRAVEL_TIME_OPEN_CLOSE

Limit for the time in seconds between the
change of the state from OPEN to
CLOSE; with 0, the time is not processed.
If the value is exceeded, the corresponding
bit will be set in CHECK_BACK. Times less
than 2 seconds cannot be monitored.

TRAVEL_TIME_CLOSE_

Maximum difference between

OPEN_TOL

TRAVEL_TIME_CLOSE_OPEN and the
current switching time

TRAVEL_TIME_OPEN_

Maximum difference between

CLOSE_TOL

TRAVEL_TIME_OPEN_CLOSE and the
current switching time

SELF_CALIB_CMD

Initiation of a device-specific calibration
procedure, manufacturer specific 0-default.

y = 0

active undamped

y = 1

active damped

x = 0

sensor indicates “valve open”

x = 1

sensor indicates “valve closed”