beautypg.com

English – Burkert Type 8642 User Manual

Page 46

background image

8642 - 45

english

FSAVE_TIME

Time in seconds after which the „Failsave“ action starts
after abortion.
The maximum value for this time is approx. 18 hours.

FSAVE_TYPE

Reaction on ”Fail Save”

0

=

valve retains the last state

1

=

valve switches according to FSAVE_VAL_D

2

=

valve becomes potential-free

FSAVE-VAL-D

The present discrete output value to use when failure

occurs.

SIMULATE

Enables the simulation of READBACK_D

CHECK_BACK

Information of the device

Bit

Information

0

in “Fail-save” position

8

Valve opens

9

Valve closes

16

The number of switching cycles pre-defined in
TRAVEL_COUNT_LIM has been exceeded

20

Time for opening exceeded

21

Time for closing exceeded

1 = active
0 = inactive

CHECK_BACK_MASK Definition of supported CHECK_BACK informtion bits

1 = supported
0 = not supported