Parameter structure of the DIAGNOSIS bit sequence

Table 8: Diagnosis of the parameter coding of the physical block

Coding of the diagnosis parameters
Values of the diagnosis bits:

0 = not set
1 = set

* Display class:
R

Display is active as long as the reason for the message is still present

A

Display will be automatically reset after reading.

Table 9: View Object of the Standard Parameters

The

View Object Standard Parameters

Bit

Notation

Description

*

4

DIA_MEM_CHKSUM

Memory checksum error

R

10

DIA_CONF_INVAL

Configuration not valid

R

11

DIA_WARMSTART

Re-start-up (warm start-up)

carried out

A

12

DIA_COLDSTART

New-start-up (cold start-up)

carried out

A