Burkert Type 2101 User Manual

Page 14

background image

14

Technicaldata

medium and pilot pressure for control function a, flow direction
below the seat (standard)

Orifice
DN

Maximum medium pressure

[bar]

Minimum pilot pressure

[bar]

Actuator size ø [mm]

Actuator size ø [mm]

50

70

90

130

50

70

90

130

10/15

25

25

-

-

5.2

4.8

-

-

20

16

20

25

9

16

32

-

8.5

16

-

5

40

6

16

50

-

10

16

5

65

5.0

16

-

5.6

80

-

10

-

100

6

Tab. 3: Medium and pilot pressure for CFA, standard

medium and pilot pressure for control function a, flow direction
below the seat reduced pressure spring force (ec04)

Orifice
DN

Maximum medium pressure

[bar]

Minimum pilot pressure

[bar]

Actuator size ø [mm]

Actuator size ø [mm]

50

70

90

130

50

70

90

130

10/15

14

16

-

-

3.2

2.5

-

-

20

6

12

25

3

6

32

-

3.5

9

-

2.5

40

2

6

16

2.5

50

-

3.5

10

-

65

-

7.5

-

3.2

80

5

Tab. 4: Medium and pilot pressure for CFA, reduced pressure

spring force (EC04)

english