beautypg.com

Brooks, Table 4-1 bench troubleshooting – Brooks Instrument 5850EM User Manual

Page 54

background image

4-4

Brooks

®

Models 5964, 5850EM

Section 4 Maintenance

Installation and Operation Manual

X-TMF-5964-5850EM-MFC-eng

Part Number: 541B121AHG

November, 2008

Table 4-1 Bench Troubleshooting

Trouble

Possible Cause

Check/Corrective Action

Actual flow overshoots setpoint by

Anticipate potentiometer out of adjustment.

Adjust anticipate potentiometer. Refer to Sections 3-5 & 3-8 .

more than 5% full scale.

Output stays at zero level regardless

Clogged Sensor tube and restrictor and/or a

Clean sensor. Refer to cleaning procedure, Section 4-2D.

of command and there is no flow

clogged orifice.

through the controller.

Closed or clogged flow path up- or downstream or

Open valve(s). Clean filter(s). Remove any foreign material from gas delivery system.

the controller.

Clogged Control Valve.

Check TP3 with the command at 100%. If the voltage is more negative than -11V,
disassemble and repair the control valve. Refer to Sections 4-3 and 4-4.

Internal reference being used as the command

Refer to Section 3-4.

source and the yellow jumper is in the wrong
position.

-15 volts applied to the valve override input

Check valve override input. Refer to Section 2-6 for terminal assignments.

Defective printed circuit board.

Replace printed circuit board. Refer to Section 4-3.

Valve voltage not returned, Pin L at common.

Check jumper for external valve return. Refer to Section 3-4.

"Valve-off" pin grounded.

Check "Valve-Off" input. Refer to Section 2-6 for terminal assignments.

Output signal stays at +6.8 Volts

Valve stuck open or leaky.

Clean and/or adjust control valve. Refer to cleaning procedure and/or Section 4-2D.

(26 mA for Current I/O Vers.) regard-
less of command and there is flow

+15 Volts applied to the valve override input.

Check the valve override terminal. Refer to Section 2-6 for terminal assignments.
through the controller.

Defective printed circuit board.

Replace printed circuit board. Refer to Section 4-3.

Command input floating.

Connect command signal. Refer to Section 2-6 for terminal assignments.

Pin D connected to common.

Remove Pin D from common.

Output signal follows set-point at

Leaky control valve

Disassemble and repair valve. Refer to Section 4-3.

higher commands but will not go to
zero.

Excessive resistance in valve voltage return line.

Reduce wiring resistance or reconfigure controller for "External Valve Return." Refer
to Section 3-4.

Output signal follows set-point at

Insufficient inlet pressure or pressure drop.

Adjust pressures, inspect in-line filters and clear/replace as necessary.

lower commands but does not reach
full scale.

Partially clogged sensor

Check calibration. Refer to Section 3-7.

Partially clogged valve.

Disassemble and repair control valve. Refer to Section 4-3.

Valve out of adjustment.

Adjust valve. Refer to Section 4-4.

Valve guide spring failure.

Check valve spring.

Controller grossly out of calibration.

Partially clogged sensor.

Clean sensor. Refer to the cleaning procedure, Section 4-2D.

Flow is higher than desired.

Controller grossly out of calibration.

Partially clogged restrictor.

Replace restrictor. Refer to Section 4-3.

Flow is lower than desired.

Controller oscillates.

Pressure drop or inlet pressure excessive.

Adjust pressures.

Oversized orifice.

Check orifice size. Refer to Section 4-6.

Valve out of adjustment.

Adjust valve. Refer to Section 4-4.

Anticipate potentiometer out of adjustment.

Adjust anticipate potentiometer. Refer to Section 3-8.

Faulty pressure regulator.

Check regulator output.

Defective printed circuit board.

Replace printed circuit board. Refer to Section 4-3.