Interpreting test results – Alpha Technologies Celltron Essential CTE-1200 AT; CTE-2200 AT; CTE-3200 AT User Manual
Page 34

28
•
To view the test results as the analyzer
displayed them when you tested the site,
scroll to
REVIEW DATA SET
and press
ENTER
.
Interpreting test results
SITE SUMMARY
The values in the
SITE SUMMARY
option are a summary of values, such as averages, from all jar posts
and straps you tested in the site.
For descriptions of these values, refer to “Menu options” in Chapter 1. To view all summary values in
SITE SUMMARY
, press
or
.
REVIEW DATA SET
The values in the
REVIEW DATA SET
option are the test results for all jar posts and straps you tested in
the site. Figure 7 labels the values.
Figure 7. REVIEW DATA SET values
percentage of the
reference value
conductance value
in siemens
voltage
jar post or
strap label
13.24V
860 S
J02B
86 % REF
03. SELECT SITE 03
REVIEW DATA SET
These values are displayed for each set of jar posts and straps in the order you tested them in the site.
If the voltage, conductance value, or percentage of the reference value is below the value you set in
the
UTILITIES
menu, a warning (?) or fail (!) symbol is displayed next to the value.
To view the data for other sets of jar posts or straps, press
or
.
Using the percentages of the reference value
You can use the percentages of the reference value from
SITE SUMMARY
for all of the jar posts
and straps to help you determine the strength of the site. Table 6 lists ranges of reference value
percentages, the condition the site is in, and the action you should take.
13.24V
860 S
J02B
86 % REF
03.
SITE 03
REVIEW DATA SET