Setting the site temperature (3. TEMP:)
To set the temperature of the site:

1. Use the temperature sensor to measure the temperature of one of the jars in the site.

2. Press

or

to scroll to selection

3. TEMP:

in the

SET PARAMETERS

and press

ENTER

.

25 °C 77 °F

SET TEMPERATURE

3. Press

or

to select the temperature in either Celsius or Fahrenheit and press

ENTER

.

Temperature will convert automatically to Celsius or Fahrenheit as you set it.

Note:

Temperature will always be shown in Celsius in the

SET PARAMETERS

menu, and on prinouts.

Setting the reference value (4. REF:)
To set a reference value:

600

SIEMENS

SET REFERENCE

1. Press

or

to scroll to

4. REF:

in

SET PARAMETERS

and press

ENTER

.

2. Press

or

to select the reference value for the site you are testing and press

ENTER

.

Note:

You can also set a reference value in the

6. CHANGE REF

option in the main

MENU.

For information about determining a reference value, refer to “Determining a reference value.”

Setting the number of volts per jar (5. VOLTS/JAR)
To set the number of volts per jar:

12

VOLTS PER JAR

SET VOLTS/JAR

1. Press

or

to scroll to

5. VOLTS/JAR

in

SET PARAMETERS

menu and press

ENTER

.

2. Press

or

to scroll to 6 or 12 VOLTS PER JAR and press ENTER to select.