Table 4. UTILITIES menu options

Option

Description

LANGUAGE

The screen displays three choices:

1. ENGLISH
2. ESPAÑOL
3. FRANÇAIS

DATE & TIME

Current date and time set in the formats from the

SET DATE FORMAT

option.

SET DATE FORMAT

Formats for the date and time:

MM/DD/YY (month/day/year) with a 12-hour clock, or

DD/MM/YY (day/month/year) with a 24-hour clock

The default is the current date and time in Central Standard Time (CST).

The default format is

MM/DD/YY with a 12-hour clock.

EDIT SITE NAME

Name of the site, which you can edit with up to 12 numbers or characters.

SET WARN/FAIL %

Percentages of the reference value for a jar and site that are thresholds to

indicate test results that fall below them. A

?

is displayed as a warning, and

a

!

is displayed if the jar or site is failing.

The defaults shown below are recommended values for jars and sites that

are in-service:

JAR FAIL: <60%

JAR WARN: <70%

SITE FAIL: <60%

SITE WARN: <70%

LOW VOLTS

Threshold amount of low voltage for a site. The defaults are:

6.1 V for a 6 V jar 6.10 V

12.6 V for a 12 V jar 12.20 V

The analyzer will use a ! to indicate a value below this threshold.

AUTO START

Toggles between AUTO START and MANUAL START.

CONTRAST

Contrast between the screen and text.