Table 4. UTILITIES menu options
Option
Description
LANGUAGE
The screen displays three choices:
1. ENGLISH
2. ESPAÑOL
3. FRANÇAIS
DATE & TIME
Current date and time set in the formats from the
SET DATE FORMAT
option.
SET DATE FORMAT
Formats for the date and time:
•
MM/DD/YY (month/day/year) with a 12-hour clock, or
•
DD/MM/YY (day/month/year) with a 24-hour clock
The default is the current date and time in Central Standard Time (CST).
The default format is
MM/DD/YY with a 12-hour clock.
EDIT SITE NAME
Name of the site, which you can edit with up to 12 numbers or characters.
SET WARN/FAIL %
Percentages of the reference value for a jar and site that are thresholds to
indicate test results that fall below them. A
?
is displayed as a warning, and
a
!
is displayed if the jar or site is failing.
The defaults shown below are recommended values for jars and sites that
are in-service:
•
JAR FAIL: <60%
•
JAR WARN: <70%
•
SITE FAIL: <60%
•
SITE WARN: <70%
LOW VOLTS
Threshold amount of low voltage for a site. The defaults are:
•
6.1 V for a 6 V jar 6.10 V
•
12.6 V for a 12 V jar 12.20 V
The analyzer will use a ! to indicate a value below this threshold.
AUTO START
Toggles between AUTO START and MANUAL START.
CONTRAST
Contrast between the screen and text.