Alpha Technologies Celltron Essential CTE-1200 AT; CTE-2200 AT; CTE-3200 AT User Manual
Page 19

13
Setting percentages for warnings and failings (E. SET WARN/FAIL %)
To set percentages for warnings and failings:
1. Press
or
to scroll to
E. WARN/FAIL %
in the
UTILITIES
menu and press
ENTER
.
2. Press
or
to scroll to the site you want to change.
3. To set
WARN
and
FAIL
percentages for the jars in
the site, press
or
and press
ENTER
after each
selection. Press
ENTER
to move to the next parameter,
the
WARN
and
FAIL
percentages for the site.
4. To select the
WARN
and
FAIL
percentages for the site,
press
or
,
and press
ENTER
after each selection.
Press
ENTER
again to return to the
UTILITIES
menu.
Setting the low voltage value (F. LOW VOLTS)
The low voltage value depends on the number of cells per jar:
Jar Voltage
Number of cells
Min. Range
Max. Range
6 V
3
3 V
7.5 V
12 V
6
6 V
15 V
To set the low voltage value for the jars in a site:
1. Press
or
to scroll to
F.
LOW VOLTS
in
the
UTILITIES
menu and press
ENTER
.
2. Press
or
to scroll to the site you want to change.
3. Press
or
to select a low voltage value (in 10 mV) for the jars in the site. Press
ENTER
.
Setting auto or manual start (G. AUTO START)
In
AUTO START
mode the test will start automatically when you connect to the jar. In
MANUAL
START
mode the analyzer will prompt you to press
ENTER
to start a test after you connect to the
jar.
AUTO START
is the factory default.
To toggle between
AUTO
and
MANUAL START
:
1. Press
or
to scroll to
G. AUTO START
in the
UTILITIES
menu and press
ENTER
.
2. Press
or
to select
AUTO START
or
MANUAL START
. Press
ENTER
.
The
UTILITIES
menu will reflect your choice until you change it again.
JAR
PERCENT REFERENCE:
WARN
%
70
FAIL
% 60
SITE
PERCENT REFERENCE:
WARN
%
70
FAIL
% 60
6.60
SET LOW VOLTAGE
AUTO START
MANUAL START
CONNECTION MODE