Setting percentages for warnings and failings (E. SET WARN/FAIL %)
To set percentages for warnings and failings:

1. Press

or

to scroll to

E. WARN/FAIL %

in the

UTILITIES

menu and press

ENTER

.

2. Press

or

to scroll to the site you want to change.

3. To set

WARN

and

FAIL

percentages for the jars in

the site, press

or

and press

ENTER

after each

selection. Press

ENTER

to move to the next parameter,

the

WARN

and

FAIL

percentages for the site.

4. To select the

WARN

and

FAIL

percentages for the site,

press

or

,

and press

ENTER

after each selection.

Press

ENTER

again to return to the

UTILITIES

menu.

Setting the low voltage value (F. LOW VOLTS)
The low voltage value depends on the number of cells per jar:

Jar Voltage

Number of cells

Min. Range

Max. Range

6 V

3

3 V

7.5 V

12 V

6

6 V

15 V

To set the low voltage value for the jars in a site:

1. Press

or

to scroll to

F.

LOW VOLTS

in

the

UTILITIES

menu and press

ENTER

.

2. Press

or

to scroll to the site you want to change.

3. Press

or

to select a low voltage value (in 10 mV) for the jars in the site. Press

ENTER

.

Setting auto or manual start (G. AUTO START)
In

AUTO START

mode the test will start automatically when you connect to the jar. In

MANUAL

START

mode the analyzer will prompt you to press

ENTER

to start a test after you connect to the

jar.

AUTO START

is the factory default.

To toggle between

AUTO

and

MANUAL START

:

1. Press

or

to scroll to

G. AUTO START

in the

UTILITIES

menu and press

ENTER

.

2. Press

or

to select

AUTO START

or

MANUAL START

. Press

ENTER

.

The

UTILITIES

menu will reflect your choice until you change it again.

JAR

PERCENT REFERENCE:

WARN

%

70

FAIL

% 60

SITE

PERCENT REFERENCE:

WARN

%

70

FAIL

% 60

6.60

SET LOW VOLTAGE

AUTO START
MANUAL START

CONNECTION MODE