Page 52: Battery mounted fuse stackup, 0 installation, continued
52
044-001-C0-00, Rev. C
Battery Terminal Connections:
Refer to the accompanying Battery Cable Kit (BCK) instructions for battery wiring
arrangement and terminal assembly procedures. During maintenance procedures, refer to the
manufacturers’ specifications for the maintenance torque requirements.
Mounting hardware requirements may vary with battery manufacturers. Use only the
hardware recommended by your particular battery manufacturer.
5.0
Installation, continued
5.3 Battery Connection
Battery Identification
Each battery contains a DATE CODE usually located on a sticker near the center of the
battery or stamped in white ink near the POS terminal. This date code must be recorded
in the battery’s maintenance log. If batteries other than those installed by Alpha are used,
consult the battery’s manufacturers’ documentation for date code type and placement.
Connections for AlphaCell Batteries
Fig. 5-5, Battery Terminal Connection
Battery Date Code
Lock W
asher
Flat W
asher
Isolation W
asher
Ring
Terminal
Ring
Terminal
Fuse
Flat W
asher
Nut
BUSS
Inline Fuse Stackup
For AlphaCell–FT
Threaded Battery
Post
Fuse
Ring
Terminal
Isolation W
asher
Flat W
asher
Lock W
asher
Bolt
(torque to 75 in-lbs on fused terminal)
BUSS
Battery Mounted Fuse Stackup
For TEL 12-105, GNB M12V155, and SMU 12-155
Bolt
(torque to 75 in-lbs on fused terminal)