beautypg.com

2 ac air conditioner specifications – Alpha Technologies Radium MiniBay User Manual

Page 36

background image

6

044-001-C0-00, Rev. C

Specifications
Capacity

5000 BTUH (sensible) @ 43ºC ambient

Maximum Operating Temperature 125º F
Electrical

8.7A @ 120VAC/60HZ maximum

4.3A @ 230VAC/60HZ maximum

4.8A @ 220VAC/50HZ maximum

UL/CUL recognized per UL50-File#SA12062 CE

Compliant

Microprocessor Controller

Displays temperature in Fahrenheit and Celsius

Programmable heating and cooling set points

Standard on/off differential 7º Fahrenheit

Programmable high/low temperature alarms

Condenser air filter maintenance indicator

Security programming access code

Integral EMI / RFI protection

24VAC input power

Operating status indicators for cooling, heating and

alarm conditions

Refrigeration System

Efficient, long lasting rotary compressor

Coil construction: Aluminum fin with copper tube

Solid core 4 stage filter drier

Pressure balancing refrigerant flow control

HCFC refrigerant 22, Chlorodifluoromethane

Evaporator Fan

Lustran ABS 6 housing and squirrel cage

Life lubricated ball bearing system

.05 HP shaded pole therm. protected motor

Maximum 247 CFM free air @120VAC/60HZ

Condenser Fan

Lustran ABS 6 housing and squirrel cage

Life lubricated ball bearing system

.05 HP shaded pole thermal protected motor

Maximum 247 CFM free air @120VAC/60HZ

3.0, AC Air Conditioner, continued

3.2 AC Air Conditioner Specifications