Standard cordex configurations, 1 standard cordex configurations – Alpha Technologies Radium MiniBay User Manual
Page 15
![background image](/manuals/317330/15/background.png)
15
044-001-C0-00, Rev. C
1.0
Overview and Specifications, continued
1.1 Standard Cordex Configurations
The Radium MiniBay may be equipped with Cordex 48-650W, 48-1kW, or 48-1.8kW AC/DC
rectifiers. Previous models were equipped with RSM 48/10 AC/DC rectifiers. Due to customer
requirements, the following illustrations may not resemble your model exactly.
RMB DC Power & Distribution Standard Configuration #1
• Cordex 48-650W 19" shelf with two rectifier modules with load LVD
• Provides 1.5A @ 48VDC, N+1
• Fully equipped shelf provides 2.6kW (54A @ 48VDC), N+0
• 2RU shelf needs 1RU above and below, convection cooled
• Heat dissipation <221 BTU/hr, per rectifier module
• Comnet GMT fuse panel, 10A/10B position -48VDC
Fig. 1-8, Radium MiniBay Standard Configuration #1
NOTE:
For units equipped with a Battery LVD, a manual reset of the battery contactor is required after the low voltage
disconnect has been tripped, if there is no resumption of AC power, and DC power is applied to the unit using
an alternate power source (DC generator).
CDX 19/23" 48-650W Shelf
2 RU
P/N 00-728-20-A010
208/240AC CXCI, Load LVD
(Battery LVD available)
GMT Fuse Panel
2 RU
P/N C016-111-10
10A/10B -48VDC
19" or 23" Heat Deflector
1 RU
CXRC 48-650W Rectifier Modules (qty 2-4)
2 RU
P/N 010-570-20-A002
Load Breakers (qty 4)
Available Sized 1-100A
19" Rack
23" Rack
0
5
10
15
20
HEAT DEFLECTOR
2
(Rack Units)
Blank Plate
P/N 00-728-20-A005