beautypg.com

Standard cordex configurations, 1 standard cordex configurations – Alpha Technologies Radium MiniBay User Manual

Page 15

background image

15

044-001-C0-00, Rev. C

1.0

Overview and Specifications, continued

1.1 Standard Cordex Configurations

The Radium MiniBay may be equipped with Cordex 48-650W, 48-1kW, or 48-1.8kW AC/DC

rectifiers. Previous models were equipped with RSM 48/10 AC/DC rectifiers. Due to customer

requirements, the following illustrations may not resemble your model exactly.

RMB DC Power & Distribution Standard Configuration #1

• Cordex 48-650W 19" shelf with two rectifier modules with load LVD

• Provides 1.5A @ 48VDC, N+1

• Fully equipped shelf provides 2.6kW (54A @ 48VDC), N+0

• 2RU shelf needs 1RU above and below, convection cooled

• Heat dissipation <221 BTU/hr, per rectifier module

• Comnet GMT fuse panel, 10A/10B position -48VDC

Fig. 1-8, Radium MiniBay Standard Configuration #1

NOTE:

For units equipped with a Battery LVD, a manual reset of the battery contactor is required after the low voltage

disconnect has been tripped, if there is no resumption of AC power, and DC power is applied to the unit using

an alternate power source (DC generator).

CDX 19/23" 48-650W Shelf

2 RU

P/N 00-728-20-A010

208/240AC CXCI, Load LVD

(Battery LVD available)

GMT Fuse Panel

2 RU

P/N C016-111-10

10A/10B -48VDC

19" or 23" Heat Deflector

1 RU

CXRC 48-650W Rectifier Modules (qty 2-4)

2 RU

P/N 010-570-20-A002

Load Breakers (qty 4)

Available Sized 1-100A

19" Rack

23" Rack

0

5

10

15

20

HEAT DEFLECTOR

2

(Rack Units)

Blank Plate

P/N 00-728-20-A005