Probe Installation Kit(s)

See the TSP-LL2’s installation instructions that came 

with the probe for the items included with the TSP-K4A 

standard probe installation kit. For chemical applications, 

see the TSP-LL2C’s installation instructions for the 

TSP -K4AS stainless steel riser cap adapter kit and the 

TSP-SSP stainless steel product float.
TSP-LL2 Probe Floats
•   Floats for 4 inch (101.6 mm) riser pipes, order: TSP-

IGF4 for gasoline applications or TSP-IDF4 for diesel 

and fuel oil

•   Floats for 3 inch (76.2 mm) riser pipes, order: TSP-IGF3 

for gasoline applications or TSP-IDF3 for diesel and fuel 

oil

•   Floats for 2 inch (50.8 mm) riser pipes, order: TSP-IGF2 

for gasoline, TSP-IDF2 for diesel and fuel oils, or TSP-

SSP stainless steel float for chemical products

Manufacturer’s Tank Chart for Each Tank

The manufacturer’s Tank Chart and other documentation 

will be used for installation and programming, and possibly 

for future reference. Keep this information — do not

discard it.

Console Installation

Console Location

The location that you select to install the console must be 

indoors in an area classified as non-hazardous (see the 

console specifications table at the beginning of the Wiring 

the Console & Modules chapter for further information). 

To get the maximum benefit from this system, install the 

console where personnel can easily make use of it; mount 

it at eye level for operator convenience. Mount the console 

level on a vertical surface between 2 feet (0.6 m) and 

6 feet (1.9 m) high using the appropriate fasteners. For 

European applications, the console must be located in a 

pollution degree 2 environment per IEC60664.

Mounting the Console

The TS-550 evo consoles must be

mounted in a location where explosive

or flammable vapors are not present,

otherwise an explosion hazard will be

created which can result in severe injury,

death, serious property damage and/or

environmental contamination.
Leave a minimum of two inches (5.1 cm)

of space around the console open to

allow for ventilation, communication port

connections, conduit and wiring. If the

ventilation louvers located on the sides

of the TS-550 evo are obstructed, the unit

may overheat and stop functioning as

intended.

Four mounting tabs are available on the outside corners 

of the console. Select fasteners that have sufficient load 

carrying capacity and which are appropriate for wall 

construction – a fully equipped TS-550evo console can 

weigh as much as 40 pounds (18 kg), so make sure that 

your fasteners (and mounting surface) can adequately 

support that much weight. In addition, plan ahead to 

make sure that there is enough room around the console 

for: conduit coming into the unit, communication port 

connections, possible incoming probe or sensor wiring, 

and for the console door to fully open for easy access. 
Note:  For questions concerning standard installation 

materials to be used for the TS-550 evo console, 

please refer to the Standard Installation Materials 

section of this manual.

Warning

Warning