Console installation – Franklin Fueling Systems TS 550 evo Fuel Management System Installation User Manual
Page 7
7
Probe Installation Kit(s)
See the TSP-LL2’s installation instructions that came
with the probe for the items included with the TSP-K4A
standard probe installation kit. For chemical applications,
see the TSP-LL2C’s installation instructions for the
TSP -K4AS stainless steel riser cap adapter kit and the
TSP-SSP stainless steel product float.
TSP-LL2 Probe Floats
• Floats for 4 inch (101.6 mm) riser pipes, order: TSP-
IGF4 for gasoline applications or TSP-IDF4 for diesel
and fuel oil
• Floats for 3 inch (76.2 mm) riser pipes, order: TSP-IGF3
for gasoline applications or TSP-IDF3 for diesel and fuel
oil
• Floats for 2 inch (50.8 mm) riser pipes, order: TSP-IGF2
for gasoline, TSP-IDF2 for diesel and fuel oils, or TSP-
SSP stainless steel float for chemical products
Manufacturer’s Tank Chart for Each Tank
The manufacturer’s Tank Chart and other documentation
will be used for installation and programming, and possibly
for future reference. Keep this information — do not
discard it.
Console Installation
Console Location
The location that you select to install the console must be
indoors in an area classified as non-hazardous (see the
console specifications table at the beginning of the Wiring
the Console & Modules chapter for further information).
To get the maximum benefit from this system, install the
console where personnel can easily make use of it; mount
it at eye level for operator convenience. Mount the console
level on a vertical surface between 2 feet (0.6 m) and
6 feet (1.9 m) high using the appropriate fasteners. For
European applications, the console must be located in a
pollution degree 2 environment per IEC60664.
Mounting the Console
The TS-550 evo consoles must be
mounted in a location where explosive
or flammable vapors are not present,
otherwise an explosion hazard will be
created which can result in severe injury,
death, serious property damage and/or
environmental contamination.
Leave a minimum of two inches (5.1 cm)
of space around the console open to
allow for ventilation, communication port
connections, conduit and wiring. If the
ventilation louvers located on the sides
of the TS-550 evo are obstructed, the unit
may overheat and stop functioning as
intended.
Four mounting tabs are available on the outside corners
of the console. Select fasteners that have sufficient load
carrying capacity and which are appropriate for wall
construction – a fully equipped TS-550evo console can
weigh as much as 40 pounds (18 kg), so make sure that
your fasteners (and mounting surface) can adequately
support that much weight. In addition, plan ahead to
make sure that there is enough room around the console
for: conduit coming into the unit, communication port
connections, possible incoming probe or sensor wiring,
and for the console door to fully open for easy access.
Note: For questions concerning standard installation
materials to be used for the TS-550 evo console,
please refer to the Standard Installation Materials
section of this manual.
Warning
Warning