beautypg.com

Wire sensor module (2wsns), Wire sensor module – Franklin Fueling Systems TS 550 evo Fuel Management System Installation User Manual

Page 21

background image

21

2-Wire Sensor Module (2WSNS)

The 2-Wire Sensor Module (2WSNS) is designed to accept 12 

sensor inputs per module, and the system as a whole can accept 

a total of 36 sensors (3 modules with 12 inputs each). The 2WSNS 

only supports standard sensors, and does not accept inputs from 

BriteSensors. Refer to the diagram below to identify some of the 

standard sensors that can be used with this module.

Note:  Standard sensors do not use digital data. They operate 

like ON–OFF switches, which are closed when no liquid is 

present and open when a liquid is detected.

2-Wire Sensor

Module

RUN

ERR

9

8

7

–Blk

+Wht

–Blk

+Wht

–Blk

+Wht

12

11

10

–Blk

+Wht

–Blk

+Wht

–Blk

+Wht

3

2

1

–Blk

+Wht

–Blk

+Wht

–Blk

+Wht

6

5

4

–Blk

+Wht

–Blk

+Wht

–Blk

+Wht

- (BLK)

(WHT)

- (BLK)

TSP-ULS

(universal liquid sensor)

TSP-HLS

(high level sensor)

Non-Hazardous

Location

Hazardous Location

Class I, Division 1, Group

D, Group IIA, Zone 0

Figure 19: 2-Wire Sensor Connections

Note: All components located in the hazardous area must be Third Party Certified and have appropriate Entity 

Parameters (see Control Drawing 000-1722 in the back of this manual for further information).

2-Wire Sensor Module

Number of Channels: 12
Safety Rating:

Class I, Division 1, Group D, [Ex ia] IIA

Entity Parameters

  Uo = 6.51 V

  Io = 2.04 mA

  Co = 500 uF

  Lo = 100 mH

  Po = 3.3 mW