10 Amp Relay Module (10ARLY)

The 10 Amp Relay Module is a non-intrinsically safe module that has 6 

identical Form C output channels. Each channel has a fuse and three 

terminals. Each channel can be configured as NO or NC with the power 

off by wiring to the appropriate terminals. A TS-550 evo console can 

accommodate up to 18 outputs (6 outputs on up to 3 modules) as space 

allows. The diagrams below illustrate two examples of positive shutdown 

upon alarm conditions.

10ARLY Module

O2

NC2

C2

NO1

NC1

C1

Relay Module disables the

hook signal to the pump

upon alarm conditions.

110/240 VAC

Electrical Panel

Line

Neutral

Switching Current 10A Max.

Switching Power 1500 VA Max.

NO6

NC6

C6

NO5

NC5

C5

NO4

NC4

C4

NO3

NC3

C3

Figure 15: Positive Submersible Control Box Shutdown

Note:  A valid dispenser hook signal coming from the AC Input Module (shown in Figure 12) is required for these 

diagrams to function as shown.

NO2

NC2

C2

NO1

NC1

C1

NO6

NC6

C6

NO5

NC5

C5

NO4

NC4

C4

NO3

NC3

C3

DISPENSER 1

10 Amp Relay Module disables power to

the dispenser upon alarm conditions.

110/240 VAC

Electrical Panel

Line

Neutral

Line

Neutral

GND

Switching Current 10A Max.

Switching Power 1500 VA Max.

10ARLY Module

Figure 16: Positive Dispenser Shutdown

Note:  If a dispenser’s current rating is higher than 10 Amps, use an appropriate extension relay.

10 Amp Relay Module Specifications

Number of Channels:

6 Form C 

Contact Rating:

10A @ 250 VAC
 or ½ hp @ 240 VAC

¼ hp @ 120 VAC