18
10 Amp Relay Module (10ARLY)
The 10 Amp Relay Module is a non-intrinsically safe module that has 6
identical Form C output channels. Each channel has a fuse and three
terminals. Each channel can be configured as NO or NC with the power
off by wiring to the appropriate terminals. A TS-550 evo console can
accommodate up to 18 outputs (6 outputs on up to 3 modules) as space
allows. The diagrams below illustrate two examples of positive shutdown
upon alarm conditions.
10ARLY Module
O2
NC2
C2
NO1
NC1
C1
Relay Module disables the
hook signal to the pump
upon alarm conditions.
110/240 VAC
Electrical Panel
Line
Neutral
Switching Current 10A Max.
Switching Power 1500 VA Max.
NO6
NC6
C6
NO5
NC5
C5
NO4
NC4
C4
NO3
NC3
C3
Figure 15: Positive Submersible Control Box Shutdown
Note: A valid dispenser hook signal coming from the AC Input Module (shown in Figure 12) is required for these
diagrams to function as shown.
NO2
NC2
C2
NO1
NC1
C1
NO6
NC6
C6
NO5
NC5
C5
NO4
NC4
C4
NO3
NC3
C3
DISPENSER 1
10 Amp Relay Module disables power to
the dispenser upon alarm conditions.
110/240 VAC
Electrical Panel
Line
Neutral
Line
Neutral
GND
Switching Current 10A Max.
Switching Power 1500 VA Max.
10ARLY Module
Figure 16: Positive Dispenser Shutdown
Note: If a dispenser’s current rating is higher than 10 Amps, use an appropriate extension relay.
10 Amp Relay Module Specifications
Number of Channels:
6 Form C
Contact Rating:
10A @ 250 VAC
or ½ hp @ 240 VAC
¼ hp @ 120 VAC