Introduction, Product description – Franklin Fueling Systems TS 550 evo Fuel Management System Installation User Manual
Page 5
5
Introduction
This manual contains installation and site preparation
instructions for Franklin Fueling Systems’s TS-550evo
console. Overall safety issues, troubleshooting information,
warranty, service, and return policies, as defined in this
manual, must be followed.
Please read this entire manual carefully. Failure to
follow the instructions in this manual may result in faulty
operation, equipment damage, injury or death. This
equipment should only be serviced by an Franklin Fueling
Systems-certified installer.
Certified Installer/Service Person
Only an Franklin Fueling Systems certified installer or
service person is allowed to access both the user interface
keypad and areas internal to the TS-550evo console.
Station Owner/Operator
The station owner or operator of the TS-550evo console is
only allowed to access the user interface keypad. Access
to areas internal to the console is strictly prohibited.
Abbreviations & Acronyms
10ARLY - 10 Amp Relay Module
2WSMS - 2-Wire Sensor Module (Intrinsically Safe)
3WSMS - 3-Wire Sensor Module (Intrinsically Safe)
420EXP - 4-20 mA EXP module
ACI - AC Input Module
420IB - 4-20mA Analog Input Module (Intrinsically Safe)
AST - Aboveground Storage Tank
ATG - Automatic Tank Gauge
CM - Controller Module
DIM - Dispenser Interface Module
FMS - Fuel Management Systems
IO - Input / Output module
IS - Intrinsically Safe
LIM - LonWorks Interface Module
PC - Personal Computer
PRB - Probe Module (Intrinsically Safe)
PS - Power Supply Module
RLY - Relay Module
SCM - Secondary Containment Monitoring
TPI - Turbine Pump Interface
TS-EXPC - TS-5 Series - Expansion Console
UST - Underground Storage Tank
Related Documentation
The system operation and programming instructions,
troubleshooting guide and console maintenance manual
are provided for your use in separate documents. Detailed
installation and testing instructions for each type of leak
detection sensor are present in the relevant manual, and,
likewise, the installation, testing, and programming of
various upgrade kits and optional accessories are also
contained in separate manuals, addenda or in one of this
document’s appendixes.
Product Description
The TS-550 evo is a modular, automatic, continuous
monitoring system that uses plug-in modules to perform
a wide variety of functions. From fuel management,
monitoring, and/or control functions the TS-550 with its
plug-in modules allows you to customize the system to
meet your needs. Purchase only those functions that
you require, and expand your system later for greater
capabilities.
The TS-550 evo’s enhanced processor and additional
memory on the CM (Controller Module) along with
the flexibility of the modular design allows for peak
performance while monitoring multiple systems. The TS-
550 can easily monitor all of your tanks, lines, sumps, and
secondary containments.
The TS-550evo console comes standard with a Controller
Module (CM), Power Supply Module (PS), and a color LCD
display and these features:
• Generates reports automatically in response to
preset / programmed conditions and alarm
• Provides audio-visual annunciation when an alar or
warning condition exists
• Performs inventory monitoring
• Is able to print reports on a compatible external Hewlett-
Packard Printer
• Can communicate via Ethernet, RS-232, RS-485, or an
optional internal fax/modem.
The TS-550 evo console optionally:
• Has six (6) open slot for additional module that can be
used to expand its capabilities
• Can support a combination of up to:
• 36 Probes (or three Probe Modules)
• 36 2-wire sensors (or three 2-Wire Sensor Modules)
• 24 3-wire or 2-wire sensors (or three 3-wire Sensor
Modules)
• 24 relay outputs (or three Relay Modules)
• 24 4-20mA inputs (or three 4-20ma Input Modules)
• 36 AC inputs (or three AC Input Modules)
• 12 4-20mA outputs & 24 AC/DC Inputs (or three
Input & Output Modules)
Example Station: If your station has 8 Submersible
Pumps, 12 Tanks, 8 Lines and 24
Sensors, you could control all of it with
your FFS TS-550evo and six plug-in
modules: a Relay Module, a Probe
Module, an Analog Input Module, an AC
Input Module and two Sensor Modules.