Introduction

This manual contains installation and site preparation 

instructions for Franklin Fueling Systems’s TS-550evo 

console. Overall safety issues, troubleshooting information, 

warranty, service, and return policies, as defined in this 

manual, must be followed.
Please read this entire manual carefully. Failure to 

follow the instructions in this manual may result in faulty 

operation, equipment damage, injury or death. This 

equipment should only be serviced by an Franklin Fueling 

Systems-certified installer.

Certified Installer/Service Person

Only an Franklin Fueling Systems certified installer or 

service person is allowed to access both the user interface 

keypad and areas internal to the TS-550evo console.

Station Owner/Operator

The station owner or operator of the TS-550evo console is 

only allowed to access the user interface keypad. Access 

to areas internal to the console is strictly prohibited.

Abbreviations & Acronyms

10ARLY - 10 Amp Relay Module

2WSMS - 2-Wire Sensor Module (Intrinsically Safe)

3WSMS - 3-Wire Sensor Module (Intrinsically Safe)

420EXP - 4-20 mA EXP module

ACI - AC Input Module

420IB - 4-20mA Analog Input Module (Intrinsically Safe)

AST - Aboveground Storage Tank

ATG - Automatic Tank Gauge

CM - Controller Module

DIM - Dispenser Interface Module

FMS - Fuel Management Systems

IO - Input / Output module

IS - Intrinsically Safe

LIM - LonWorks Interface Module

PC - Personal Computer

PRB - Probe Module (Intrinsically Safe)

PS - Power Supply Module

RLY - Relay Module

SCM - Secondary Containment Monitoring

TPI - Turbine Pump Interface

TS-EXPC - TS-5 Series - Expansion Console

UST - Underground Storage Tank

Related Documentation

The system operation and programming instructions, 

troubleshooting guide and console maintenance manual 

are provided for your use in separate documents. Detailed 

installation and testing instructions for each type of leak 

detection sensor are present in the relevant manual, and, 

likewise, the installation, testing, and programming of 

various upgrade kits and optional accessories are also 

contained in separate manuals, addenda or in one of this 

document’s appendixes. 

Product Description

The TS-550 evo is a modular, automatic, continuous 

monitoring system that uses plug-in modules to perform 

a wide variety of functions.  From fuel management, 

monitoring, and/or control functions the TS-550 with its 

plug-in modules allows you to customize the system to 

meet your needs.  Purchase only those functions that 

you require, and expand your system later for greater 

capabilities.  
The TS-550 evo’s enhanced processor and additional 

memory on the CM (Controller Module) along with 

the flexibility of the modular design allows for peak 

performance while monitoring multiple systems.  The TS-

550 can easily monitor all of your tanks, lines, sumps, and 

secondary containments.   
The TS-550evo console comes standard with a Controller 

Module (CM), Power Supply Module (PS), and a color LCD 

display and these features: 
•   Generates reports automatically in response to 

preset / programmed conditions and alarm

•   Provides audio-visual annunciation when an alar or 

warning condition exists

•   Performs inventory monitoring
•   Is able to print reports on a compatible external Hewlett-

Packard Printer

•   Can communicate via Ethernet, RS-232, RS-485, or an 

optional internal fax/modem.

The TS-550 evo console optionally:
•   Has six (6) open slot for additional module that can be 

used to expand its capabilities

•   Can support a combination of up to:

•  36 Probes (or three Probe Modules)
•   36 2-wire sensors (or three 2-Wire Sensor Modules)
•   24 3-wire or 2-wire sensors (or three 3-wire Sensor 

Modules)

•   24 relay outputs (or three Relay Modules) 
•   24 4-20mA inputs  (or three 4-20ma Input Modules)
•   36 AC inputs (or three AC Input Modules)
•   12 4-20mA outputs & 24 AC/DC Inputs (or three 

Input & Output Modules) 

Example Station:  If your station has 8 Submersible 

Pumps, 12 Tanks, 8 Lines and 24 

Sensors, you could control all of it with 

your FFS TS-550evo and six plug-in 

modules: a Relay Module, a Probe 

Module, an Analog Input Module, an AC 