N-x144_iom_25, Table 6: x144 e-flowmeter operational flow ranges – Cla-Val X144 Technical Manual User Manual
Page 25
Table 6: X144 e-FlowMeter Operational Flow Ranges
22
Table 7: X144 e-FlowMeter Analog Range (4-20mA Scaling): Factory Settings
If required, the factory settings of the e-FlowMeter can be adjusted. A Cla-Val USB Adapter Cable is required and can be
ordered by contacting the factory at 800.942.6326.
Go to
http://www.cla-val.com/software-driver-library.php for software/instructions.
SECTION 5: Specifications (continued)
Line Size
inches (mm)
*2"
(50mm)
(100-49
Body)
2-1/2"
(65mm)
3"
(80mm)
4"
(100mm)
6"
(150mm)
8"
(200mm)
10"
(250mm)
12"
(300mm)
16"
(400mm)
Minimum Flow
(GPM)
10
10
15
25
60
100
160
230
360
Maximum Flow
(GPM)
210
300
460
800
1800
3150
4950
7000
11000
Minimum Flow
(l/S)
0.65
0.65
1.0
1.5
3.8
6.3
10.0
15
23
Maximum Flow
(l/S)
13.3
18.9
29
50
110
200
310
440
700
Notes:
* Pulse Width = 250ms.
**2" X144 e-FlowMeter may be installed on new valves only. Consult Factory for Angle Pattern Applications
Port Style
Line Size
inches (mm)
**2"
(50)
(100-49
Body)
2-1/2"
(65)
3"
(80)
4"
(100)
6"
(150)
8"
(200)
10"
(250)
12"
(300)
14"
(350)
16"
(400)
18"
(450)
20"
(500)
24"
(600)
30"
(750)
Full Port
Valves
4mA = 0
(GPM -
l/s)
20mA Range
(GPM)
260
375
575
1000
2250
3900
6000
8750 10500 14000 17500 22000 31000 52000
20mA Range
(l/s)
16.4
23.7
36.3
63.1
140
245
380
550
660
880
1100
1390
1950
3280
Full Port
Pulse
Weight*
Gal/Pulse
5
6.5
9.5
17
38
65
100
150
175
235
290
365
515
865
l/Pulse
19
25
36
65
145
245
380
565
660
890
1100
1380
1950
3275
Reduced
Port
Valves
4mA = 0
(GPM-
l/s)
20mA Range
(GPM)
not available
675
1600
2900
4500
5650
7750
9350
Consult Factory
20mA Range
(l/s)
42.5
100
180
285
355
490
590
Reduced
Port
Valves
Pulse
Weight*
Gal/Pulse
11.5
26
48
75
95
130
155
l/Pulse
44
99
180
285
360
495
585