Section 2: Installation of the X144 e-FlowMeter (continued)

2.4 - Step-by-Step Instructions: Mechanical Installation

CAUTION:

BEFORE removing pipe plug, make sure that the pressure in the valve has been bled

off to prevent injury to personnel or damage to non-waterproof equipment

1) Isolate valve/pipe from pressure and flow.

2) Remove pipe plug on INLET boss of valve.

3) Remove sensor/head unit from threaded pipe insert

by unscrewing the knurled lock and sliding the sensor

out of the threaded insert (Figure 2-3).

Set aside sensor head, making sure to protect the

sensor tip

4) Apply Teflon

®

thread tape and/or pipe thread compound to tapered threads on pipe insert,

shown below (Figure 2-4):

5) Straighten the Measurement Cylinder by hand to create a slight angle (Figure 2-5); Tighten the

locking collar on the straight threads of the insert (2); and tighten the thumb

set screw (3); to maintain the slight angle of the Measurement Cylinder.