Section 2: Installation of the X144 e-FlowMeter (continued)

2.5 - Step-by-Step Instructions: Electrical Installation for General Applications

Figure 2-12: X144 e-FlowMeter Cable Options

1) Connect the wire marked “4-20mA” to the proper recording/measurement device. Connect that

device per manufacturer’s recommendations. If no logging/DAQ/SCADA system is available,

attach the “4-20mA” wire to the ground of the power supply.

2) Connect the wire marked “24 VDC” to either 12 VDC or 24 VDC, as available.

3) If possible, use handheld multi-meter to verify mA readings prior to leaving installation.

a) When there is no flow present, the X144 e-FlowMeter should read very close to 4.0 mA.

4) A possible power supply for the X144 e-FlowMeter is the Cla-Val X143MP Micro Turbine Power

Generator. (See Figure 2-16, Page 14)

Note:

AC/DC converters must be properly grounded in order to prevent electronic noise.

12

24 VDC

white wire

4-20 mA

brown wire

Connect brown wire

to ground wire if

no accessory devices

are being used

Note: When connecting 4-20mA
circuit, place all reading/ logging
equipment (if any) in series

X144 e-FlowMeter™

Data

Logger

Digital

Multi-Meter

SCADA
System

GSM/GPRS

Telemetry

Key: optional accessory equipment not supplied with e-FlowMeter

green

blue

red

grey

pi

n

k

y

e

llo

w

w

hi

te

b

ro

wn

1

2

3

4

5

6

7

8

10 - 30 VDC

+

-

Power Supply/Battery