Technical specifications, 1. astat, Ibp plus, general specifications – GE Industrial Solutions ASTAT-IBP Plus User Manual
Page 9

Voltage Ratings 3ph AC Systems
Up to 600V, +10%, -15% for QI3xDP ASTAT-IBP
Plus series
Freq. Range
50/60
Hz
Control range of 45-65 Hz
Control
Control system
Digital system with microcontroller
Specifications
Starting ramp with progressive increase in voltage and
current limitation
Initial voltage (pedestal)
%
30 - 95 Un
Starting torque
%
10 - 90 Mdirect start
Kick start
%
95 Un (90% Mdirect start), adjustable 0 to 999 ms
Motor unit ratio (N)
0.4 - 1.2
Current limit (starting)
1 to 4.5 (Ir/In) Max 4.5 In
Acceleration ramp time
s
1 to 45 (standard or linear ramp up)
Bypass
Direct control of a bypass contactor
Brake time by ramp
s
1 to 60 (1 to 60 in secondary ramp) adjustable independently of starting
ramp time (types: standard, pump control or linear ramp down)
Monitoring
Motor current, line voltage (1), power, power factor and elapsed time
Running
External control
Start - Stop
Acceleration phase
Adjustable time
Stop phase
Power cut-off / Ramp / Pump control
Inputs / Outputs Inputs
4 digital optocoupled. Two fixed (Start , Stop), and 2 programmable (I3, I4)
1 Analog 0-5VDC for Tachogenerator input feedback
Outputs
2 Programmable relays (1r, 3r); 1 fixed relay (2r)
1 Analog 0-10VDC output for current metering
Protections
Current limit
Adjustable 1 to 4.5 (Ir
/
In) Max 4.5 In
Overload
IEC class 10 and 20 ; NEMA class 10, 20 and 30 all selectable
Cool-down time after
overload trip
See Restart Times on page 4-10
Loss on input phase
s
Trip at 3
Thyristor short circuit
ms
Trip at 200
Heatsink overheating
ms
Trip at 200
Motor thermistor
ms
Trip at 200 if thermistor impedance > response value
Loss on output phase
s
Trip at 3
Stalled rotor
ms
Trip at 200
Supply frequency error
Hz
If f < 45 or f > 65, will not start
Overcurrent
100 to 150% In; trip time adjustable from 0 to 99 sec.
Undercurrent
0 to 99% In; trip time adjustable from 0 to 99 sec.
Overvoltage (1)
100 to 130% Un; trip time adjustable from 0 to 99 sec.
Undervoltage (1)
0 to 50% Un; trip time adjustable from 0 to 99 sec.
Error (CPU)
ms
60
Memory
4 former errors
Long start time
s
2 x ta (ta = acceleration ramp time)
Environmental
Temperature
°C
0 to +55 (derate output current by 1.5% /
°C above 40°C)
conditions
Relative humidity
%
95% without condensation
Maximum altitude
m
3000 (derate output current by 1% / 100m above 1000m)
Mounting position
Vertical
Protection Degree
IP00, UL Open
Standards
cUL, UL
UL, cUL conforming to UL508
Conducted & radiated emissions
Conforming IEC 947 -4-2, Class A
Electrostatic discharges
Conforming to IEC 1000-4-2, level 3
Radioelectric interference
Conforming to IEC 1000-4-6, level 3 and to IEC 1000-4-3, level 3
Immunity to fast trasients
Conforming to IEC 1000-4-4, level 3
Immunity to Surge Voltage
Conforming to IEC 1000-4-5, level 3
3-1. ASTAT
®
-IBP Plus, General specifications
3. Technical Specifications
3-1
(
I
Actual measured motor current
Im
Maximum starting current desired
In
Nominal motor nameplate FLA
Ir
ASTAT rated nameplate FLA
L
Current limit for starting Im/Ir
Lmax
450/N
Mdirect start Full voltage starting torque
N
In/Ir
SF
Service factor
Un
Full line voltage
Note: (1) Monitors L1
Abbreviations