MULTIPULSE DRIVE PANEL
12 GE Energy ©2012 GE Company All Rights Reserved
4 Drive
Terminal Board I/O
Any of the AF-600 FP and AF-650 GP terminal
board I/O points which are not already in use
for proper operation of the bypass panel are
available for customer use. The meanings and
connection diagrams for these I/O points are
well described and illustrated in the
DET - 767
AF- 650 GP Design and
Installation Guide
DET - 618
AF- 650 GP Programming
Guide
DET - 768
AF-600 FP Design and
Installation Guide
DET - 620
AF-600 FP Programming Guide
Which are supplied with your panel
documentation package. However there are
several I/O points, which will find frequent use
in panel applications that they are described
below for convenience.
Relay 1 – 01, 02, 03
Programmable contacts
Relay 2 – 04, 05, 06
Programmable contacts.
20, 21, 22, 50, 53, 55
Used for drive speed reference inputs. The
speed pot can be connected to points 50, 53,
and 55. The customer supplied 0-10 VDC or 4-
20 mA signal can also be utilized. Customer
supplied 0-10 VDC signal is connected to
points 20 and 22. Customer supplied 4-20 mA
signal is connected to points 20 and 21.
29 and 12
Used for issuing preset speed command to
drive. The speed at which the motor will run
can be set via drive function code C20.
1, 2, 3, 4, 5 DEVICE NET
62, 63, 66, 67, CS
PROFIBUS/BACNET
79, 80 LONWORKS
68, 69, 61
RS485 Port
39, 42 Analog output
27 Digital output
(Drive Ready)