Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual
Page 9

■
■ GE Zenith Controls
7 ■
■
MX150/MX250 Series Modbus Network Card (71R-2200)
Appendix A
(cont’d)
Read Only Register List
Holding Reg.
Bit Coil Description
Value
40025
S1 Voltage (Phase A-B), Raw A/D
Raw A/D Value - See Note 1
40026
S1 Voltage (Phase B-C), Raw A/D
Raw A/D Value - See Note 1
40027
S1 Voltage (Phase C-A), Raw A/D
Raw A/D Value - See Note 1
40028
S2 Voltage (Phase A-B), Raw A/D
Raw A/D Value - See Note 1
40029
S2 Voltage (Phase B-C), Raw A/D
Raw A/D Value - See Note 1
40030
S2 Voltage (Phase C-A), Raw A/D
Raw A/D Value - See Note 1
40031
S1 Period Count
Raw Value - See Note 2
40032
S2 Period Count
Raw Value - See Note 2
40049
Total S1 Fails
40050
Total Transfers to S2
40051
Days Powered Up
40052
Time S1 Available (MSR)
Hours
40053
Time S1 Available (LSR)
Hours
40054
Time S2 Available (MSR)
Hours
40055
Time S2 Available (LSR)
Hours
40056
Unused
40057
Unused
40058
Unused
40059
Unused
40060
Unused
40061
Unused
40062
Unused
40063
Exerciser Schedule Status
0 81 Exerciser Type
1 = Clock, 0 = Timer
1 82 Load/No Load Exerciser (Timer Exerciser Only)
1 = Load
2 83 User can set load exercises (Clock Exerciser Only) 1 = Yes
3 84 Unused
4 85 Unused
5 86 Unused
6 87 Unused
7 88 Unused
[15:8]
Timer Exerciser Run Duration
Minutes
40064
MX Status 3
0 89 Exerciser Pending
1 = Exerciser Pending
1 90 Exerciser Bypassed
1 = Exerciser Bypassed
2 91 Unused
3 92 Unused
4 93 Unused
5 94 Unused
6 95 Unused
7 96 Unused
40065
Unused
40066
Unused
40067
Unused