Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual
Page 14
■
■ 12
GE Zenith Controls ■
■
MX150/MX250 Series Modbus Network Card (71R-2200)
2.
Registers 40031 and 40032 contain unscaled
frequency values. In order to obtain a full-scale
frequency value, use the following formula:
Scales Frequency + (20,000,000 / Period Count)
Notes:
1.
Registers 40025 - 40030 contain unscaled voltage
values In order to obtain a full-scale voltage value,
use the following formula:
Voltage = (A/D Raw Value / 192) x
Full Scale Voltage (Register 40021)
Timer Value
P 111b
W-W3, Unbypassed
110b
W-W3, YE bypassed
101b
T-T3, Unbypassed
011b
Y-T3, YN bypassed
010b
U 000b
Reason Code
Description
0 S1
Fail
1 S2
Fail
2
S1 Phase Imbalance
3
S2 Phase Imbalance
4 S2
Start
5 S2
Stop
6 Sync
Fail
7 Load
Shed
8 ATS
Inhibit
9 Phase
Rotation
10 Remove
Test
11 Local
Test
12 S1-S2
Volt.
Imbalance
13
S1-S2 Freq. Imbalance
14
CT Xfr S1>S2
15
CT Xfr S2>S1
16 Xfr
S1>S2
17 Xfr
S2>S1
18
19
20 No
Xfr
21 OLC
22 STE
23
S1 UV Fail
24
S1 OV Fail
25
S1 UF Fail
26
S1 OF Fail
27
S2 UV Fail
28
S2 OV Fail
29
S2 UF Fail
30
S2 OF Fail
31 S1
Restore
32
S2 to Open
33 Exerciser
34 Remote
Test
Network
35 Remote
Inhibit
36 Local
Inhibit
37 S2
Avail
38 S2
Off
Appendix A
(cont’d)
Read Only Register List