beautypg.com

Appendix e, 485 multi-drop connection – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual

Page 19

background image

GE Zenith Controls

17

MX150/MX250 Series Modbus Network Card (71R-2200)

Appendix E

MASTER

DEVICE

A

B

MX150/250

WITH

MODBUS

CARD

SLAVE #1

A

B

MX150/250

WITH

MODBUS

CARD

SLAVE #2

A

B

MX150/250

WITH

MODBUS

CARD

SLAVE #3

SEE NOTE 1

A

B

N

OTE

:

1.

TERMINATION JUMPER (J6), LOCATED ON THE MODBUS
CARD, MUST BE CONNECTED ON THE LAST SLAVE IN THE
CHAIN. (REFER TO FIGURE 3 FOR JUMPER POSITIONS)

2.

A MAXIMUM OF 247 SLAVES CAN BE ADDRESSED ON
THE MODBUS NETWORK.

3.

RECOMMENDED TWISTED PAIR WIRE IS BELDEN 8471,
16 AWG (GE ZENITH PART # WMW-453).

4.

FOLLOW STANDARD RS485 WIRING (INSTALL A REPEATER
IF THE WIRE LENGTH EXCEEDS 4,000 FT. OR FOR EVERY 32
DEVICES ON THE NETWORK).

RS