Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual
Page 8
■
■ 6
GE Zenith Controls ■
■
MX150/MX250 Series Modbus Network Card (71R-2200)
Appendix A
(cont’d)
Read Only Register List
Holding Reg.
Bit Coil Description
Value
40005
Timer Countdown Value
Seconds
40006
S1 Voltage (Phase A-B)
Volts
40007
S1 Voltage (Phase B-C)
Volts
40008
S1 Voltage (Phase C-A)
Volts
40009
S2 Voltage (Phase A-B)
Volts
40010
S2 Voltage (Phase B-C)
Volts
40011
S2 Voltage (Phase C-A)
Volts
40012
Unused
40013
S1 Frequency
Freq Value = scaled value/10
40014
Unused
40015
S2 Frequency
Freq Value = scaled value/10
40016
Unused
40017
Total Transfers to S1
40018
Unused
40019
Serial Number (MSR)
40020
Serial Number (LSR)
40021
Nominal Full-Scale Voltage
40022
MX Network Configuration 0
0 41 Unused
1 42 Unused
2 43 Unused
3 44 Unused
4 45 Unused
5 46 Closed Transition Configured
1 = Configured
6 47 In-Phase Monitor Configured
1 = Configured
7 48 ATS Type
1 = Delay, 0 = Standard
40023
MX Network Configuration 1
0 49 S12 Auto/Manual Option
1 = Configured
1 50 S5 Auto/Manual Bypass Option
1 = Configured
2 51 Phase Sequence Check Option
1 = Configured
3 52 S2 Overfrequency Option
1 = Configured
4 53 S2 Overvoltage Option
1 = Configured
5 54 S1 Overfrequency Option
1 = Configured
6 55 S1 Underfrequency Option
1 = Configured
7 56 S1 Overvoltage Option
1 = Configured
40024
MX Network Configuration 2
0 57 Phase Imbalance Configured
1 = Configured
1 58 Unused
2 59 Closed Transition Configured
1 = Configured
3 60 Pre-Load Disconnect
1 = Configured
4 61 Post-Load Disconnect
1 = Configured
5 62 Open Loop Transfer Option
1 = Configured
6 63 Unused
7 64 Controller Type
1 = MX150/250, 0 = MX200