Appendix a, Read only register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual
Page 10
■
■ 8
GE Zenith Controls ■
■
MX150/MX250 Series Modbus Network Card (71R-2200)
Appendix A
(cont’d)
Read Only Register List
Holding Reg.
Bit Coil Description
Value
40068
Timer ID 1
0 97 Unused
1 98 Unused
2 99 A6/A62 Timer Running
1 = Running
3 100 T Timer Running
1 = Running
4 101 DT Timer Running
1 = Running
5 102 T3/W3 Timer Running
1 = Running
6 103 W Timer Running
1 = Running
7 104 DW Timer Running
1 = Running
40069
T or W Timer Countdown Value
Seconds
40070
T3/W3 Timer Countdown Value
Seconds
40071
A6/A62 Timer Countdown Value
Seconds
40072
MX Firmware Revision
Ver = Value/10
40073
Modbus Card Firmware Revision
Ver = Value/100
40074
Unused
40075
Unused
40076
Unused
40077
Most Recent Event Pointer
40082
Unused
40083
Unused
40099
System Time – Day of Week
Holding Reg.
Bit Coil Description
Range
Notes
40102
Exerciser
Record
– Hour
0 - 23
40103
Exerciser
Record
– Minute
0 - 59
40104
Exerciser
Record
– Month
1 - 12
Not writeable for Daily
or
Weekly
Exercisers
40105
Exerciser
Record
– Day of Month
1 - 31
Max val. depends on month, year
Not writeable for Daily
or
Weekly
Exercisers
40106
Exerciser
Record
– Day of Week
1 = Sun., 7 = Sat.
Writeable for Weekly Exercisers Only
40107
Exerciser
Record
– Ex. Duration
0 - 600 minutes
40108
Exerciser
Record
– Load/No Load
1 = Load, 0 = No Load
Writeable ONLY if Factory
Configured for Load Exercisers
40109
Unused
40110
Exerciser Schedule Selection
0 = Off
1 = Daily (1 Day)
2 = Weekly (7 Day)
3 = Bi-Weekly (14 Day)
4 = 4 Week (28 Day)
5 = Calendar (365 Day)