Appendix b, Read/write register list – GE Industrial Solutions MX150_MX250 Modbus Network Card User Manual
Page 16
■
■ 14
GE Zenith Controls ■
■
MX150/MX250 Series Modbus Network Card (71R-2200)
Appendix B
(cont’d)
Read/Write Register List
Holding Reg. Bit Coil Description
Range
Notes
HR 40094 - 40098 MUST ALL be written with a Write Multiple Holding Register Command
40094
System
Time
– Hour
0 - 23
40095
System
Time
– Minute
0 - 59
40096
System
Time
– Day
1 - 31
Max val. depends on month, year
40097
System
Time
– Month
1 - 12
40098
System
Time
– Year
0 - 255, 0 = Year 2000
40100
Daylight Savings Time
1 = ATS follows DST
HR 40101 - 40109 MUST ALL be written with a Write Multiple Holding Register Command
HR's listed as "Not Writeable" under certain conditions must be written as zeros
HR40101-40110 are for CDP Programmable Exercisers Only
40112
System Busy Control
0 113 Command to Bypass In-Phase Monitor 1 = Bypass In-Phase Monitor
1 114 Confirm Bypass In-Phase Monitor
1 = Confirm
2
115
Unused
3
116
Unused
4
117
Unused
5
118
Unused
6
119
Unused
7
120
Unused
40113
Net Control 2
0 121 Bypass Pending Exerciser
1 = Bypass
1 122 Cancel Exerciser Bypass
1 = Cancel Bypass
2
123
Unused
3
124
Unused
4
125
Unused
6
127
Unused
7
128
Unused