■ GE Zenith Controls
5 ■
■
MX150/MX250 Series Modbus Network Card (71R-2200)
Appendix A – Read Only Register List
Holding Reg.
Bit Coil Description
Value
40001
MX Status 0
0
1 Automatic Transfer Relay
1 = On, 0 = Off
1
2 ATS Not in Auto Mode
1 = Not in Auto
2
3 General Purpose Alarm
1 = Alarm Active
3
4 Unused
4
5 Load Test or Fast Load Test Running
1 = Running
5
6 Load, No Load, Fast Load Test Status
1 = Running
6
7 S2 Available
1 = Available
7
8 S1 Available
1 = Available
40002
MX Status 1
0
9 SN Limit Switch
1 = On, 0 = Off
1 10 SE Limit Switch
1 = On, 0 = Off
2 11 SNO Limit Switch
1 = On, 0 = Off
3 12 SEO Limit Switch
1 = On, 0 = Off
4 13 S2 Phase Rotation - Valid only if 3ph and S2 Avail 1 = CW, 0 = CCW
5 14 S1 Phase Rotation - Valid only if 3ph and S1 Avail 1 = CW, 0 = CCW
6 15 Number of Phases on S2
1 = Three, 0 = One
7 16 Number of Phases on S1
1 = Three, 0 = One
40003
MX Status 2
0 17 Unused
1 18 S5 Active
1 = On, 0 = Off
2 19 S12 Active
1 = On, 0 = Off
3 20 Load Shed (LS) Active
1 = On, 0 = Off
4 21 Q7 Active
1 = On, 0 = Off
5 22 Q3 Active
1 = On, 0 = Off
6 23 Closed Transfer Relay (CTR) Active
1 = On, 0 = Off
7 24 Transfer Mode Select (TMS) Active
1 = On, 0 = Off
40004
Timer ID 0
0 25 Timer Bit 0
See Table 1
1 26 Timer Bit 1
See Table 1
2 27 Timer Bit 2
See Table 1
3 28 Unused
4 29 Unused
5 30 Unused
6 31 Unused
7 32 Unused
8 33 Timer Active
1 = Timer Running
9 34 S1 Position Status
1 = S1 Position
10 35 S2 Position Status
1 = S2 Position
11 36 Unused
12 37 Unused
13 38 Unused
14 39 Unused
15 40 Unused