5

the neutral conductor should be provided in the building wiring

installation.

This is permanently connected equipment , it must be installed

by qualified maintenance personnel.

For permanently connected equipment: make sure that a

readily accessible disconnect device is incorporated in the

building installation wiring.

To reduce the risk of fire, connect only to a circuit provided with

branch circuit overcurrent protection with an ampere rating in

accordance with the IEC/EN 60934 standard or your local

electrical code and have a contact air gap of at least 3 mm.

Uninterruptible power supply

output power

240V

6K

40 amp

2-pole circuit breaker

10K

63 amp

2-pole circuit breaker

You can connect four extended battery modules to the

uninterruptible power supply.

Earthing connection is essential before connecting to the

building wiring terminal.

2.2 Operation

Do not disconnect the earth conductor cable from the UPS or

the building wiring terminals in any time since this would cancel

the protective earthing of the UPS system and all connected

loads.

The UPS output terminal block may be electrically active even if

the UPS system is not connected to the building wiring

terminal.

In order to completely disconnect the UPS, firstly press the

OFF button, and then disconnect the mains lead.