2 dimension and weight, 3 operating environment – PowerWalker Battery pack for VFI 10000P_RT LCD User Manual
Page 55

51
Current
26.4A@230Vac
44.0A@230Vac
Power Factor
≥
0,99 @100% Nominal Load
≥
0,98 @50% Nominal Load
≥
0,95 @25% Nominal Load
THDI
< 5 %@Full load and battery full charged
Battery & Charger
Battery
180VDC/5Ah
240VDC/9Ah
Current
39A
48A
Charger current
>1A
>1.7A
7.2 Dimension and Weight
Dimension
(W*D*H) mm
438*698*129
438*704*215.5
Net Weight (KG)
46
82.5
Gross Weight (KG)
50
87.5
7.3 Operating Environment
Item
Specification/Function
Standards/Comments
Cooling
Force Air Cooling
Operating
Temperature
Range
0°C ~ 40 °C
Nominal power & continuous
operating mode
Storage
Temperature
-15°C~60°C
UPS
0~35°C
Battery
Relative
Humidity
0-95%
No condensing
Altitude
<1000m for Nominal power
Over 1000 m the power
derating is 1 % every 100 m
Acoustic
Noise
<55dB