55

BUS Over Voltage

Alarm Code:21

Indicates that the UPS
get BUS over voltage
fault because of BUS.

The UPS transfers to
Bypass mode if supporting
the load

BUS Under Voltage

Alarm Code:22

Indicates that the UPS
get BUS under voltage
fault

The UPS transfers to
Bypass mode if supporting
the load

BUS Unbalance

Alarm Code:23

Indicates that the positive
BUS voltage and
negative BUS voltage are
too lopsided to fault

The UPS transfers to
Bypass mode if supporting
the load

BUS Short

Alarm Code:24

Indicates that the BUS
voltage decrease very
fast

Contact your service
representative

BUS Softstart Fail

Alarm Code:25

Indicates that the BUS
could not soft start
successfully

Contact your service
representative

Inv Over Voltage

Alarm Code:32

Indicates that the UPS
get invert over voltage
fault

The UPS transfers to
Bypass mode if supporting
the load

Inv Under Volatge

Alarm Code:33

Indicates that the UPS
get inverter under voltage
fault

The UPS transfers to
Bypass mode if supporting
the load

Inv Softstart Fail

Alarm Code:34

Indicates that the inverter
could not soft start
successfully

Contact your service
representative

Charger Fail

Alarm Code:15

Indicates that the UPS
has confirmed the
charger has failed

The UPS turns off the
charger until the next power
recycle. Contact your
service representative

Battery Over Voltage

Alarm Code:16

Indicates that the battery
voltage is too high

The UPS will turn off the
charger until the battery
voltage is normal

Fatal eeprom Fault

Alarm Code:A3

Indicates that the UPS
could not read eeprom
successfully

Contact your service
representative

Negative power Fault

Alarm Code:

E1

In parallel system

power

of UPS is negative

Redundancy mode

the fault

UPS turn to fault mode
without output

Increase mode

UPS1&

UPS2 turn to fault mode