background image

48

4. Disconnect the internal battery connectors

5. Replace the UPS front cover

6.3 Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every 6

months by connecting the UPS to utility power. The batteries charge to

90% capacity in approximately 4 hours. However, it is recommended

that the batteries charge for 48 hours after long-term storage.

Check the battery recharge date on the shipping carton label. If the date

has passed and the batteries were never recharged, do not use the UPS.

Contact your service representative.

When to Replace Batteries

When the status summary screen displays the UPS fault icon with the

“Service Battery” alarm and the audible alarm sounds continuously, the

batteries may need replacement. Contact your service representative to

order new batteries.

6.4 Testing Batteries

For a battery test, please check:

The batteries must be fully charged.

The UPS must be in Normal mode with no active alarms.

The load must be higher than 10%.

To test batteries:

1 Connect the UPS to utility power for at least 48 hours to charge

the batteries.

2 Press the

button for one second to go to the main menu

selection and scroll down to the Control menu using the

button.

3 Press the

button to enter the Control menu.

4 Use the

button to scroll to the Battery Test option.

5 Press the

button to start the battery test.