background image

30

4) Set the main maintenance switch or static switch from “UPS” to

“BPS”, then switch off the main output breaker and the input

breaker and mains breaker, then the UPS will shut down.

5) Connect the cable and wire of the added UPS according to the

Figure.4-5.a and Figure.4-5.b

6) Switch on the input breakers and mains breaker, and make

sure that every UPS work in bypass mode.

7) Switch on the O/P breakers and main O/P breaker

transfer the

main maintenance switch or static switch from “BPS” to “UPS”.

8) Press the

button of one UPS, each UPS would start to turn

on, after that, the two UPS should work parallel in Line mode.

How to remove a single UPS from a parallel system:

1) Firstly a main maintenance mechanical switch or static switch

should be installed for the parallel system.

2) Ensure the bypass is normal and the bypass setting is “enable”,

press the

button to turn off the UPS system, and the UPS

system will work in bypass mode.

3) Transfer the main maintenance switch or static switch from

“UPS” to “BPS”, then switch off the output breakers and the

input breakers and mains breaker for the two UPS, and the

UPS would shut down.

4) Switch off the main O/P breaker and O/P breaker for the UPS

system.

5) Remove the wanted UPS and cables and wires.

6) Switch on the mains breaker and input breaker of the reserved

UPS, make sure the UPS work in bypass mode.

7) Switch on the O/P breaker and main O/P breaker.

8) Transfer the main maintenance switch or static switch from

“BPS” to “UPS”, and press the

button to turn on the UPS,

and the UPS would start to turn on, then the UPS should work

in Line mode.