6) Turn on the input breakers for the two parallel UPS.

7) Pressing

button continuously for more than 1 second for

one UPS of the system, then the system will start to turn on and

enter line mode.

8) Regulate the output voltage of the each UPS

separately, and

check if the output voltage difference between the two ups is

less than 0.5V. If the difference is more than 0.5V, the UPS

need to be regulated.

9) If the difference output voltage is less than 0.5V, switch on the

output breakers for the two UPS separately and switch on the

main O/P breakers, then the system will work normally in

parallel.

The output wiring requirement as follows:

When the distance between the UPS in parallel and the

breaker panel is less than 10 meters, the length difference

between input and output cable of the UPSs is required to be

less than 20%.

When the distance between the UPS in parallel and the

breaker panel is more than 20 meters, the length difference

between input and output cable of the UPSs is required to be

less than 5%.

How to join a new UPS to a parallel system:

1) Firstly a main maintenance mechanical switch or static switch

should be installed for the parallel system.

2) Regulate the output voltage of the new UPS: check if the output

voltage difference between the new UPS and the parallel

system is less than 0.5V.

3) Ensure the bypass of the parallel system is normal and the

bypass setting is “enable”, then press the

button to turn off

the UPS, then UPS will work in bypass mode.