4. Power cables connection & Startup

This section explains:

Access to terminal block

Common input sources connection

Separate input sources connection

Frequency converter connection

UPS initial startup

Use cable cross section and protective device specification

Model

6K

10K

Protective earthing conductor

Min cross section

4mm

2

(10AWG)

6mm

2

(8AWG)

Input L, N, G

Min conductor cross section

4mm

2

(10AWG)

6mm

2

(8AWG)

Input fuse

60A

80A

Output L,N,

Min conductor cross section

4mm

2

(10AWG)

6mm

2

(8AWG)

External Battery Cabinet

Positive Pole(+), Negative

pole(-), Neutral Pole

Min conductor cross section

4mm

2

(10AWG)

2.5mm

2

*2

(12AWG*2)

External Battery Cabinet Fuse

60A

80A

in Positive Pole(+), Negative

pole(-), Neutral Pole

The UPS does not have an automatic protection device against current
backfeed. It is suggested that install an external isolating device ,which
is shown in the following illustration. Check for hazardous voltage
between all terminals before operating on this circuit.