Parallel cable loss

Alarm Code: E2

In parallel system

parallel cable disconnect

Disconnect parallel cable
one turn to fault mode

Parallel system
battery status

Alarm Code: E6

UPS1 connect battery

UPS2 without battery

Check battery connect
status

Line input different

Alarm Code: E7

Parallel system

UPS1

line ok

UPS2 line loss

Check the line input

Bypass input different

Alarm Code: E8

Parallel system

UPS1

bypass ok

UPS2 Bypass

loss

Bypass different

not allow

turn on UPS. Check bypass
input

Power strategy
different

Alarm Code: E9

Parallel system

UPS OP

mode

normal

converter

HE

different

Check UPS OP mode, Keep
OP mode be the same

Rate power different

Alarm Code: EA

Parallel system rate
power different

Rate power different

not

allow turn on UPS. Keep
rate power be the same

HE in parallel

Alarm Code: EB

Parallel system

OP

mode set as HE

HE not allow in parallel
system

change OP mode