PowerWalker Battery pack for VFI 10000P_RT LCD User Manual
Page 60

56
Parallel cable loss
Alarm Code: E2
In parallel system
,
parallel cable disconnect
Disconnect parallel cable
one turn to fault mode
Parallel system
battery status
Alarm Code: E6
UPS1 connect battery
,
UPS2 without battery
Check battery connect
status
Line input different
Alarm Code: E7
Parallel system
,
UPS1
line ok
,
UPS2 line loss
Check the line input
Bypass input different
Alarm Code: E8
Parallel system
,
UPS1
bypass ok
,
UPS2 Bypass
loss
Bypass different
,
not allow
turn on UPS. Check bypass
input
Power strategy
different
Alarm Code: E9
Parallel system
,
UPS OP
mode
(
normal
,
converter
,
HE
)
different
Check UPS OP mode, Keep
OP mode be the same
Rate power different
Alarm Code: EA
Parallel system rate
power different
Rate power different
,
not
allow turn on UPS. Keep
rate power be the same
HE in parallel
Alarm Code: EB
Parallel system
,
OP
mode set as HE
HE not allow in parallel
system
,
change OP mode