PowerWalker Battery pack for VFI 10000P_RT LCD User Manual

Page 46

background image

42

















Figure. 5-16 Measurement menu tree

5.4.5 The control menu

By pressing

on the menu of “Control”, the display would enter

the next control menu tree.

1) Start Battery Test: this is one command that control the UPS to

do the battery test.

2) Clear EPO status: once EPO status is enabled, the UPS output

would be cut off. To recover to normal status, first EPO

connector should be closed, and enter this menu to clear EPO

status, then UPS would stop alarm and recover to Bypass

model. And UPS needs be turned on by manual operation.

3) Reset Fault status: when fault occurs, UPS would keep in Fault

mode and alarm. To recover to normal status, enter this menu