PowerWalker AS_400 Card User Manual

As-400 card quick guide

background image

AS-400 Card Quick Guide

V.2.0

Product Outlook

1

3

Installation

2

Product Introduction

The AS400 communication card provides contact closures for remote monitoring
your UPS. To meet different application requirement, the AS400 card is capable of
selection the status of the dry-contact signal (active close or active open) by setting
jumper. This suitable applications are listed below:

IBM Server, Personal PC & Workstations equipments

Auto-controlled industrial equipment & communication applications

Step 1: Remove cover of Intelligent
Slot on the rear panel of the UPS.

Cover of
Intelligent Slot

Step 2: Insert AS400 card into Intelligent
Slot.

Step 3: The cover of AS400 should attach
close to the rear panel. Using screwdriver,
secure the AS400 to the UPS chassis with
2 screws.

Step 4: Use the 9-pin communication
cable to connect UPS and equipment to
implement the remote monitoring and
control.

9-pin communication cable

Internal circuit of DB-9 port

Specifications

4

Pin Assignment

Pin Assignment Function I/O

Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9

UPS Failure

UPS Audible Alarm

GND (Common for Pin 4)

Remote Shutdown

Common for relays

Bypass Active

Low Battery

UPS On

Utility Failure

O/P
O/P

Power Ground

I/P

Power Supply

O/P
O/P
O/P
O/P

AC status

Reason

AO status

Pin 1 & Pin 5 connected Pin 1 & Pin 5 disconnected UPS internal failure

Pin 2

Pin 2

& Pin 5 connected

& Pin 5 disconnected

UPS failure, utility failure,
low battery, bypass active

Pin 6

Pin 6

Bypass active

Pin 7 & Pin 5 connected Pin 7 & Pin 5 disconnected Battery voltage is low
Pin 8 & Pin 5 connected Pin 8 & Pin 5 disconnected UPS is in inverter mode
Pin 9 & Pin 5 connected Pin 9 & Pin 5 disconnected Utility failure

& Pin 5 connected

& Pin 5 disconnected

Function Description

P.S. The shutdown pin (pin4 & pin3) only accepts 3-10s high level signal to perform
the UPS shutdown.

Top View

Side View

1

N

4

1

4

8

W

UPS Failure

UPS Audible

Alarm

Remote Shutdown

Common

Bypass

Low Battery

UPS On

Utility Failure

2K/0.1W

Electric Parameter of DB-9 port

Parameter Symbol MAX. Min. UNIT

Diode

Relay

DC Current

Reverse Voltage

Forward Current

Peak Forward Current

DC Voltage

DC Current

6

6

50

1

24

1.0

mA

V

mA

A
V
A

Resistor*

V

R

I

F

I

F(peak)

V

DC

I

DC

I

R

1

-

-

-

-

-

Note: It’s required to retain the DC current lower than 6mA. Otherwise, it’s
necessary to add one resistor within DC current limitation in the serial loop of
Remote Shutdown. (e.g. 2K resistor with at least 0.1W rating power). Refer to
diagrams in Application.