6. UPS Maintenance

This chapter explains how to:

Care for the UPS and batteries

Transport the UPS

Store the UPS and batteries

Test the batteries

Recycle the used Battery or UPS

6.1 UPS and Battery Care

For the best preventive maintenance, keep the area around the UPS

clean and dust-free. If the atmosphere is very dusty, clean the outside of

the system with a vacuum cleaner. For full battery life, keep the UPS at

an ambient temperature of 25°C (77°F)

Note: The batteries in the UPS are rated for a 3-5 year service life. The

length of service life depends on the frequency of usage and ambient

temperature. Batteries used beyond expected service life will often have

severely reduced runtimes. Replace batteries at least every 5 years to

keep units running at peak efficiency.

6.2 Transporting the UPS

NOTE: The internal UPS batteries MUST be disconnected before

transport.

CAUTION: The following procedure should be performed or supervised

by personnel knowledgeable about batteries and the required precaution.

Keep unauthorized personnel away from batteries.

If the UPS requires any type of transportation, the batteries must be

disconnected (but not removed) before the unit is transported:

1. Verify that the UPS is off and disconnected from utility power.

2. Place the UPS on a flat, stable surface with the front of the cabinet

facing you.

3. Remove the UPS front cover