3. Application Note
3.1 INIT* pin Operation
Each I-7000 module has a build-in EEPROM to store con-
figuration information such as address, type, baudrate and other
information. Sometimes, user may forget the configuration of the
module. Therefore, the I-7000 have a special mode named INIT
mode, to help user to resolve the problem. The INIT mode is
setting as Address=00, baudrate=9600bps, no checksum
To enable INIT mode, please following these steps:
Step1. Power off the module
Step2. Connect the INIT* pin with the GND pin.
Step3. Power on
Step4. Send command $002(cr) in 9600bps to read the configu-
ration stored in the modules EEPROM.
Refer to 7000 Bus Converter User Manual Sec.5.1 and
Getting Start for more information.
3.2 Module Status
PowerOn Reset or Module Watchdog Reset will let all
output goto PowerOn Value. And the module may accept the
hosts command to change the output value.
Host Watchdog Timeout will let all output goto Safe
Value.The modules status (readed by command ~AA0) will be
04, and the output command will be ignored.