beautypg.com

4 #aan – B&B Electronics I-7060 - Manual User Manual

Page 33

background image

33

I-7000 DIO Manual

Rev:B1.2

2.4 #AAN

Description : Read Digital Input Counter from channel N
Command : #AAN[CHK](cr)
#

delimiter character

AA

address of reading module (00 to FF)

N

channel to read

Response : Valid Command :

!AA(Data)[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no
response.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

(Data) digital input counter value in decimal, from 00000 to 65535
Example :
Command : #032

Receive : !0300103

Read address 03 digital input counter value of channel 2, re-
turn value 103.

Command : #025

Receive : ?02

Read address 02 digital input counter value of channel 5, re-
turn the channel is not available.

Related Command :
Sec.2.12 $AACN
Note :
The command is useless for I-7042/42D/43/43D/66/66D/67/67D.