beautypg.com

23 ~aa5v – B&B Electronics I-7060 - Manual User Manual

Page 55

background image

55

I-7000 DIO Manual

Rev:B1.2

2.23 ~AA5V

Description : Set PowerOn/Safe Value.
Command : ~AA5V[CHK](cr)
~

delimiter character

AA

address of setting module (00 to FF)

5

command for set PowerOn/Safe Value

V

P = set current output as PowerOn Value, S = set current
output as Safe Value

Response : Valid Command :

!AA[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no
response.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example :
Command : @01AA

Receive : >

Output address 01 value AA, return success.

Command : ~015P

Receive : !01

Set address 01 PowerOn Value, return success.

Command : @0155

Receive : >

Output address 01 value 55, return success.

Command : ~015S

Receive : !01

Set address 01 Safe Value, return success.

Command : ~014P

Receive : !01AA00

Read address 01 PowerOn Value, return PowerOn Value AA.