Installation guide, Ea10 series – Veris Industries EA10 SERIES Install User Manual
Page 10

ZL0102-0A
PAGE 10
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
05126
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
EA10 SERIES
Start
End
N
R/W
Name
Type
Units
Scale Factor
Contents
Description
40081
40081
1
R
SC_DC_Current
int16
Amps
SC_DC_
Current_SF
Measured
Combined current value (sum of string amps)
40082
40083
2
R
SC_DC_AmpHour uint32
AH
SC_DC_AH_SF
Metered
Accumulated amps supplied by combiner (sum of
string amp-hours). Only positive (+) current flow
is accumulated. Negative (-) current flow is not
accumulated.
40084
40084
1
R
SC_DC_Voltage
int16
Volts
SC_DC_
Voltage_SF
Measured
Combined voltage value (not supported)
40085
40085
1
R
SC_Internal_
Temp
int16
°C
N/A
Measured
Internal temperature of the combiner (not
supported)
40086
40086
1
R
SC_Input_DC_
Current_SF
int16
SF
N/A
Configured
DC input current scale factor
40087
40087
1
R
SC_Input_DC_
AH_SF
int16
SF
N/A
Configured
DC input amp-hour scale factor