DeviceNet Network Scanner DVPDNET-SL
2.6 Digital Indicator
The digital indicator provides the following two functions:
DVPDNET
POWER
MS
NS
1) Displaying the node address and error messages of DVPDNET-SL .
2) Displaying the error message of slave.
Note:
z
When the module works normally, the digital displayer will show its own node ID.
z
When "E1" and "03" are on display continuously, it indicates that the error that "E1" refers to
occurs in the slave of node 03.
z
When the error codes such as "E7" and "E1" are on display, please refer to section 11.2 for the
correction.