2 data mapping areas, 3 i/o mapping table (as master mode), Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual
Page 15
DeviceNet Network Scanner DVPDNET-SL
4.2 Data Mapping Areas
The data mapping introduced in this chapter is the data mapping between PLC MPU and DVPDNET-SL. The
mapping relation is unchanged and user has no right to revise this area.
Max 8 PLC DVPDNET-SL modules can be connected to PLC’s left side. After all DVPDNET-SL are connected
to DVP-SV, DVP-SV will distribute data mapping areas to every DVPDNET-SL.
DVPDNET
DVP28SV
RUN
STOP
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVPDNET
DVPDNET
The index of DVPDNET-SL is its unit number. The first DVPDNET-SL on the left hand side of DVP-SV is No. 1,
the following DVPDNET-SL modules are No. 2, No. 3, No. 4 and so on.
Mapped D registers
DVPDNET-SL
index
Output mapping
Input mapping
1
D6250 ~ D6497
D6000 ~ D6247
2
D6750 ~ D6997
D6500 ~ D6747
3
D7250 ~ D7497
D7000 ~ D7247
4
D7750 ~ D7997
D7500 ~ D7747
5
D8250 ~ D8497
D8000 ~ D8247
6
D8750 ~ D8997
D8500 ~ D8747
7
D9250 ~ D9497
D9000 ~ D9247
8
D9750 ~ D9997
D9500 ~ D9747
4.3 I/O Mapping Table (as master mode)
As DVPDNET-SL of unit No. 1 serves as master mode, the data mapping areas are distributed as below table.
Output mapping area
Input mapping area
D register
Mapping area
Data length
D register
Mapping area
Data length
D6250 ~ D6281
Explicit message
program request
32 words
D6000 ~ D6031
Explicit message
program response
32 words
D6282 ~ D6285
Bit-strobe
command
4 words
D6032 ~ D6035
Status of nodes in
the scan list
4 words
D6286 Reserved 1word
D6036
DVPDNET-SL
status
1 word
D6287 ~ D6476
DeviceNet output
data
190 words
D6037 ~ D6226
DeviceNet input
data
190 words
D6477 ~ D6497 Reserved
21 words
D6227 ~ D6247
Reserved
21 words
DVP-PLC Operation Manual
12