beautypg.com

2 data mapping areas, 3 i/o mapping table (as master mode), Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual

Page 15

background image

DeviceNet Network Scanner DVPDNET-SL

4.2 Data Mapping Areas

The data mapping introduced in this chapter is the data mapping between PLC MPU and DVPDNET-SL. The

mapping relation is unchanged and user has no right to revise this area.

Max 8 PLC DVPDNET-SL modules can be connected to PLC’s left side. After all DVPDNET-SL are connected

to DVP-SV, DVP-SV will distribute data mapping areas to every DVPDNET-SL.

DVPDNET

DVP28SV

RUN

STOP

DVPDNET

DVPDNET

DVPDNET

DVPDNET

DVPDNET

DVPDNET

DVPDNET

The index of DVPDNET-SL is its unit number. The first DVPDNET-SL on the left hand side of DVP-SV is No. 1,

the following DVPDNET-SL modules are No. 2, No. 3, No. 4 and so on.

Mapped D registers

DVPDNET-SL

index

Output mapping

Input mapping

1

D6250 ~ D6497

D6000 ~ D6247

2

D6750 ~ D6997

D6500 ~ D6747

3

D7250 ~ D7497

D7000 ~ D7247

4

D7750 ~ D7997

D7500 ~ D7747

5

D8250 ~ D8497

D8000 ~ D8247

6

D8750 ~ D8997

D8500 ~ D8747

7

D9250 ~ D9497

D9000 ~ D9247

8

D9750 ~ D9997

D9500 ~ D9747

4.3 I/O Mapping Table (as master mode)

As DVPDNET-SL of unit No. 1 serves as master mode, the data mapping areas are distributed as below table.

Output mapping area

Input mapping area

D register

Mapping area

Data length

D register

Mapping area

Data length

D6250 ~ D6281

Explicit message
program request

32 words

D6000 ~ D6031

Explicit message
program response

32 words

D6282 ~ D6285

Bit-strobe
command

4 words

D6032 ~ D6035

Status of nodes in
the scan list

4 words

D6286 Reserved 1word

D6036

DVPDNET-SL
status

1 word

D6287 ~ D6476

DeviceNet output
data

190 words

D6037 ~ D6226

DeviceNet input
data

190 words

D6477 ~ D6497 Reserved

21 words

D6227 ~ D6247

Reserved

21 words

DVP-PLC Operation Manual

12