DeviceNet Network Scanner DVPDNET-SL

10.3 Ladder Diagram Program

This section introduces how to edit the ladder diagram program to meet the control request of DeviceNet network.

Control

request

When X0=ON, VFD-L AC motor drive runs;
When X1=ON, VFD-L AC motor drive stops;
After VFD-L has run for 6 seconds and at this time the running frequency still has not
reached the designated frequency, Y0 of DVP28SV=ON.

Explanation of PLC Program

MOV

H1

D6287

X0

MOV

K2000

D6288

X1

TMR

T0

K60

LD<>

K2000

D6037

MOV

H12

D6287

When X0=ON, VFD-L starts up and

its target frequency is 20Hz.

When X1=ON, VFD-L stops running.

Y0 will be ON in DVP28SV if the
frequency of VFD-L has not reached
20Hz after starting up for 6 seconds

X0

T0

Y0

( )

DVP-PLC Operation Manual

38