3 specifications, Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual
Page 5
DeviceNet Network Scanner DVPDNET-SL
1.3 Specifications
PLC that DVPDNET-SL supports
Item
Specification
PLC Model
DVPDNET-SL supports PLC MPU which can be extendable in its left side
g. DVP-SV, DVP-EH2_L, DVP-SX2, DVP-SA2, DVP10MC11T etc.)
DeviceNet
Interface
Item
Specification
Transmission
method
CAN
Electrical
isolation
500V DC
Interface Removable
connector
(5.08mm)
Transmission
cable
TAP-CB01 cable and TAP-CB02 cable are recommended. (The shielded wire
must be grounded and the cable should be away from power line)
DeviceNet network provides direct current: 11~25V, 28mA(typical value),
125mA impulse current(24 VDC)
Voltage
DeviceNet
Communication
Item
Specification
Explicit connection, IO polled connection, bit-strobe connection, COS/CC
connection
Message type
Baud rate
Standard mode: 125 kbps; 250 kbps; 500 kbps
Extended mode: 10 kbps; 20 kbps; 50 kbps; 125 kbps; 250 kbps; 500 kbps;
800kbps; 1M kbps
Environment
Item
Specification
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Operation
0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage
-25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Vibration/shock
resistance
Standard: IEC 61131-2、IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)
Certificates
IEC 61131-2, UL508
DVP-PLC Operation Manual