DeviceNet Network Scanner DVPDNET-SL

4 Configuration of DVPDNET-SL

4.1 Configuration through DeviceNet Builder Software

Before DVPDNET-SL starts to work normally, it must be configured through DeviceNet Builder

software.

4.1.1 Selection

of

Communication Channel

Max 8 DVPDNET-SL modules can be connected to the left side of PLC and every DVPDNET-SL is a

communication channel. When there are three DVPDNET-SL modules connected to PLC’s left side and

DeviceNet Builder software is on line, the following dialog box will pop up for selecting the current channel.

Parameter

Explanation

The unit No. of the first DVPDNET-SL(DNET Scanner)on the left side of PLC is 1.

PLC’s left side can be connected with max 8 DVPDNET_SL. The further
DVPDNET-S is from PLC MPU, the larger its unit No is.

Unit No.

DVPDNET-SL’s name in DeviceNet Builder software.

Name

For displaying the current mode of DVPDNET-SL: master mode or slave mode.

Code

The register areas which PLC MPU distributes to DVPDNET-SL.The areas are
mainly used to receive the message from DeviceNet Slave and the data from
slave in the bus will be automatically updated to these registers.

Input

mapping

Output

mapping

The register areas which PLC MPU distributes to DVPDNET-SL. The areas are

mainly used to control DeviceNet slave and the control data in these registers will
be automatically sent to DeviceNet slave in the bus. Slave will take some action
accordingly after receiving the data.

DVP-PLC Operation Manual

8