4.1.2 Setup of Scan Module

The following dialog is for setting DVPDNET-SL’s current mode: master mode or slave mode.

Parameter

Explanation

Master

mode

For setting DVPDNET-SL as master mode.

Scan

interval

time

The cycle time for master to send and receive the real time data after real-time
data connection is successful.

Timeouts

EPR)

The result value of the parameter multiplied by 4. (Unit:ms)
Master assumes that the slave is offline if it receives no response from slave after
timeout.

Extended
baud rate

The parameter gets effective only in master mode.
Selecting “Startup” activates the function of extended baud rate.
Select the appropriate baud rate according to actual demand then.

Slave mode For setting DVPDNET-SL as slave mode

Bit-strobe Reserved; no actual purpose now.

Polled

The parameters get effective only in slave mode.
The filled byte number corresponds to the data length for output and input as
DVPDNET-S is taken as slave. “Sending data length” corresponds to “Output
length” and “Receiving data length” corresponds to “Input length”.

COS/CC

Reserved; no actual purpose now.

Device
mapping
address

For AH modes specially; no actual purpose now.

Note: These parameters and the configuration information are downloaded to DVPDNET-SL together.