2 setup of scan module, Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual
Page 12
DeviceNet Network Scanner DVPDNET-SL
4.1.2 Setup of Scan Module
The following dialog is for setting DVPDNET-SL’s current mode: master mode or slave mode.
Parameter
Explanation
Master
mode
For setting DVPDNET-SL as master mode.
Scan
interval
time
The cycle time for master to send and receive the real time data after real-time
data connection is successful.
Timeouts
(
EPR)
The result value of the parameter multiplied by 4. (Unit:ms)
Master assumes that the slave is offline if it receives no response from slave after
timeout.
Extended
baud rate
The parameter gets effective only in master mode.
Selecting “Startup” activates the function of extended baud rate.
Select the appropriate baud rate according to actual demand then.
Slave mode For setting DVPDNET-SL as slave mode
Bit-strobe Reserved; no actual purpose now.
Polled
The parameters get effective only in slave mode.
The filled byte number corresponds to the data length for output and input as
DVPDNET-S is taken as slave. “Sending data length” corresponds to “Output
length” and “Receiving data length” corresponds to “Input length”.
COS/CC
Reserved; no actual purpose now.
Device
mapping
address
For AH modes specially; no actual purpose now.
Note: These parameters and the configuration information are downloaded to DVPDNET-SL together.
DVP-PLC Operation Manual
9