Devicenet network scanner dvpdnet-sl – Delta DVP-0204520-03 User Manual
Page 35
DeviceNet Network Scanner DVPDNET-SL
VFD-L
parameter
Set value
Explanation
02-00
4
Transmit the frequency of VFD-L via RS485
communication.
02-01
3
Control operation of VFD-L via RS485
communication.
09-00
1
Set the node address of VFD-L in Modbus to 1.
09-01
1
Set the communication rate of VFD-L in Modbus 9600
09-04
1
Set the communication format of VFD-L in Modbus to
7, E, 1, ASCII.
10.2 How to Configure Network by DeviceNet Network Configuration Tool
1) Configuration of DeviceNet slave
1> Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System
Channel”, and the “Serial Port Setting” dialog box will appear as below.
2> Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address,
baud rate and communication format. Click on “OK” after configuration is finished.
Item
Function
Default
COM Port
COM port on the PC to be used to
communicate with DVP-SV
COM1
Address
Communication address of DVP-SV
01
Baud rate
Communication speed between the PC and
DVP-SV
9,600 (bps)
Data Bits
7
Parity Even
Parity
Stop Bit
Communication protocol between the PC
and DVP-SV
1
Mode
Communication mode between the PC and
DVP-SV
ASCII
DVP-PLC Operation Manual
32